Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 5/10years |
Still deciding? Get samples of US$ 2199/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Models
|
80K
|
100K
|
110K
|
125K-HV
|
Input DC
|
||||
Max. input voltage
|
1100 V
|
|||
Rated voltage
|
600 V
|
720 V
|
||
Start-up voltage
|
195 V
|
|||
MPPT voltage range
|
180-1000 V
|
|||
Max. input current
|
9*26 A
|
10*26 A
|
||
Max. short circuit current
|
9*40 A
|
10*40 A
|
||
MPPT number/Max. input strings number
|
9/18
|
10/20
|
||
Output AC
|
||||
Rated output power
|
80 kW
|
100 kW
|
110 kW
|
125 kW
|
Max. apparent output power
|
88 kVA
|
110 kVA
|
121 kVA
|
137.5 kVA
|
Max. output power
|
88 kW
|
110 kW
|
121 kW
|
137.5 kW
|
Rated grid voltage
|
3/N/PE, 220 V / 380 V, 230 V / 400 V
|
3/PE, 480 V
|
||
Rated grid frequency
|
50 Hz / 60 Hz
|
|||
Rated grid output current
|
121.6 A / 115.5 A
|
152.0 A / 144.3 A
|
167.1 A / 158.8 A
|
150.4 A
|
Max. output current
|
133.7 A / 127.0 A
|
167.1 A
|
183.8 A
|
165.4 A
|
Power factor
|
>0.99 (0.8 leading - 0.8 lagging)
|
|||
THDi
|
<3%
|
|||
Efficiency
|
||||
Max. efficiency
|
98.7%
|
99.0%
|
||
EU efficiency
|
98.3%
|
98.5%
|
||
Protection
|
||||
DC reverse-polarity protection
|
Yes
|
|||
Short circuit protection
|
Yes
|
|||
Output over current protection
|
Yes
|
|||
Surge protection
|
DC Type II / AC Type II
|
|||
Grid monitoring
|
Yes
|
|||
Anti-islanding protection
|
Yes
|
|||
Temperature protection
|
Yes
|
|||
Strings monitoring
|
Yes
|
|||
I/V Curve scanning
|
Yes
|
|||
Integrated AFCI (DC arc-fault circuit protection)
|
Yes (1)
|
|||
Integrated PID recovery
|
Optional
|
|||
Integrated DC switch
|
Yes
|
|||
Integrated AC switch
|
Optional
|
|||
General Data
|
||||
Dimensions (W*H*D)
|
1050*567*314.5 mm
|
1065*567*344.5 mm
|
||
Weight
|
82 kg
|
91 kg
|
||
Topology
|
Transformerless
|
|||
Self-consumption (night)
|
<2 W
|
|||
Operating ambient temperature range
|
-30 ~ +60°C
|
|||
Relative humidity
|
0-100%
|
|||
Ingress protection
|
IP66
|
|||
Cooling concept
|
Intelligent redundant fan-cooling
|
|||
Max. operation altitude
|
4000 m
|
|||
Grid connection standard
|
G98 or G99, VDE-AR-N 4105 / VDE-AR-N 4110 / VDE V 0124, EN 50549-1, VDE 0126 / UTE C 15 / VFR:2019, CEI 0-21, C10/11, NRS 097-2-1,
TOR, EIFS 2018.2, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530
|
|||
Safety/EMC standard
|
IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4
|
|||
Features
|
||||
DC connection
|
MC4 connector
|
|||
AC connection
|
OT terminal (max. 185 mm²)
|
|||
Display
|
LCD
|
|||
Communication
|
RS485, Optional: Wi-Fi, GPRS, PLC
|